Table of Contents |
---|
...
Relevant Devices
Description | Qty | Source | Part Number | |
---|---|---|---|---|
Barometer/Humidity Sensor | 1 | Vaisala | PTU300 | |
Serial Interface Cable | 1 | Vaisala | 19446ZZ | |
RS-232 to Ethernet Adapter | 1 | Lantronix | UDS2100 | This is the version with two serial ports (but standard 9-pin RS-232 connectors) |
...
...
Relevant Functional Block Diagram
...
Software Actions
Action | Notes | |
---|---|---|
1 | Read pressure value | Value reported as telemetry (see below) |
2 | Read temperature value | Value reported as telemetry (see below) |
3 | Read relative humidity value | Value reported as telemetry (see below) |
...
Required Adjustable Settings
Setting | When Needed | Notes | ||
---|---|---|---|---|
Build | Observing | Maintenance | ||
Pressure measurement frequency | Yes | No | Maybe | Set in configuration file. If this needs to be changed, edit configuration file, re-install, and then restart dispatcher. |
Temperature measurement frequency | Yes | No | Maybe | See pressure. |
Relative humidity measurement frequency | Yes | No | Maybe | See pressure. |
...
Required Telemetry
Parameter | Report Frequency | Purpose | Notes | |
---|---|---|---|---|
1 | Pressure measurement | Once every 5 sec [TBC] | Environmental monitoring | Managed through configuration file |
2 | Temperature measurement | Once every 5 sec [TBC] | Environmental monitoring | See pressure. |
3 | Relative humidity measurement | Once every 5 sec [TBC] | Environmental monitoring | See pressure. |
...
Required Alarms
Parameter | Threshold | Notes | |
---|---|---|---|
1 | Time of last connection | More than 10 seconds | |
2 |
...
Relevant Datasheets & Manuals
Description | File | Source | |||||
---|---|---|---|---|---|---|---|
1 | Vaisala PTU300 User’s Guide (2019 version; device purchased in 2014) |
| |||||
2 | Lantronix UDS 2100 Quick Start Guide |
| https://www.lantronix.com/products/uds2100/#tab-docs-downloads | ||||
3 | Lantronix UDS 2100 User Guide |
|
...
Relevant Software
Description | Files | |||||
---|---|---|---|---|---|---|
1 | Python 2 software written by a student some years back. These lines of code were used to read values from the Vaisala while it was installed at Keck. That installation was using a USB interface on a Windows machine. Not sure if the current serial interface will change anything here. |
| ||||
2 | As part of the KROOT distribution, there is a SerialStream interface which manages connections to and from serial hosts. This includes managing Lantronix connections. |
...
Dispatcher Implementation
Keyword | Value | Type |
---|
CONN
On or Off - controls whether or not the connection to the Lantronix is on or off.
Can be used if the Vaisala needs to be unplugged and moved, for example.
Boolean which is writable.
IP
IP address of the Lantronix box.
String set in the configuration file, only readable.
PORT
Port for the Lantronix box that talks to the correct serial device.
String set in configuration file, only readable.
RETVAL | Value returned by Vaisala. | String. The format is set in the configuration file. Only readable. |
TIME | Time stamp of when the last RETVAL was received. | Unix timestamp (binary) or time stamp (ascii). Only readable. |
PRES | Pressure value in units of hPa. | Double value from RETVAL, read only. |
RELH | Relative humidity in %. | Double value from RETVAL, read only. |
TEMP | Temperature in deg C. | Double value from RETVAL, read only. |
DISP#STA | Dispatcher status. | Enum and read only. If value is 4 or “Not Connected” the connection to the Vaisala or the Lantonix is not available. If value is 3 or “Connecting” the dispatcher is attempting to connect to the Vaisala through the Lantronix. |
DISP#CONN | IP address and port separated by a colon. | Read only string, set by configuration file |
DISP#DEV | Device name | Read only string, set by configuration file |
Configuration | Value | Explanation |
---|---|---|
ip | 192.168.23.126 | IP address of the Lantronix box. |
port | 10001 | Port that is used for Vaisala, this is port 1. |
format_str | form 9.4 "P=" P " " U6 6.4 "T=" T " " U3 6.4 "RH=" RH " " U4 \r \n | Format statement of the output from the Vaisala. At dispatcher start up and at every new connection, this value is sent to the Vaisala. The #.# sets the number of characters (first # ) and the second # sets the number of characters after the decimal point. There must be a space between the characters that notes what the value is (such as P=) and the actual value (the P). The code uses the characters (P=, RH= or T=) to determine what the next value is. |
poll_time | 5 | Time between reads of the Vaisala in seconds. |