Introduction

Each cryostat will have two ion pumps attached. One will be operated continuously and the second will sit idle as a backup. Each pump has a dedicated controller (for a total of four in the system).

...

Proposal: name each ion pump with respect to its camera (Green/Red) and the side of the spectrometer it is on (Echelle/Collimator)

...

Relevant Devices

Description

Qty

Source

Part Number

Ion Pump Controller

4

Gamma

SPC-1-P-S-1-US110-E-S-N

Ion Pump

4

Gamma

3SDI1V5KNN (3S TiTan)

Air Cables

4

Gamma

10K-SC10-10K (10 m)

Vacuum Cables

4

Custom

Note there are two pumps per cryostat. One will be operated and the second will sit idle as a backup.

Each pump has a dedicated controller.

-

...

Relevant Functional Block Diagram

...

Software Actions

Green controller 1Green controller 2Green controller 2Red controller 1Red controller 1Red controller 2Red controller 2

Action

Notes

1

SG needs to update

23

Green controller 1: take pressure measurement

Value GRN_ION_E: Read telemetry

Pressure, Voltage, and Current values reported as telemetry (see below)

4

Green controller 2: take pressure measurement

Value reported as telemetry (see below)

5

Red controller 1: take pressure measurement

Value reported as telemetry (see below)

6

Red controller 2: take pressure measurement

Value reported as telemetry (see below)

7

Green controller 1: turn pump on

82

GRN_ION_C: Read telemetry

3

RED_ION_E: Read telemetry

4

RED_ION_C: Read telemetry

5

GRN_ION_E: turn pump on

These controls should have a lock applied so they cannot be accidentally switched.

6

GRN_ION_E: turn pump off

97

GRN_ION_C: turn pump on

10
8

GRN_ION_C: turn pump off

119

RED_ION_E: turn pump on

12
10

RED_ION_E: turn pump off

1311

RED_ION_C: turn pump on

14
12

RED_ION_C: turn pump off

...

Required Adjustable Settings

...

Parameter

Report Frequency

Purpose

Notes

1

SG needs to update

2

3

Green controller 1 pressure value

Once per minute (TBC)

Monitor green cyrostat pressure

4

Green controller 2 pressure value

Once per minute (TBC)

Monitor green cyrostat pressure

5

Red controller 1 pressure value

Once per minute (TBC)

Monitor red cyrostat pressure

6

Red controller 2 pressure value

Once per minute (TBC)

Monitor red cyrostat pressure

...

Parameter

Threshold

Notes

1

Green controller 1 pressure high

TBC

Only one pump per cyrostat will be in operation at any time.

The alarm system would need to know which pump/controller is in operation at any time to monitor the correct pressure value.

2

Green controller 2 pressure high

TBC

3

Red controller 1 pressure high

TBC

4

Red controller 2 pressure high

TBC

5

6

High Voltage turns off

7

8

9

...

Relevant Datasheets & Manuals

...

Device Command List for KPF

Noted as a ‘draft’ at this point as need to finalize Arc Detection command setting.

View file
nameIon pump controller commands - DRAFT.xlsx

...