Relevant Functional Block Diagram
...
Note while that we will have separate cables, however the python code below software interface does not differentiate by cable when it combines sensor IDs into a list.
Software Actions
...
Action
...
Notes
...
Read temperature values from all sensors
...
Required Adjustable Settings
...
Setting
...
When Needed
...
Notes
...
Build
...
Observing
...
Maintenance
...
Sensor location table(s)
...
YES
...
NO
...
MAYBE
...
Sensor Read Frequency
...
YES
...
NO
...
MAYBE
Device Setup Parameters
The current device settings can be listed through a telnet connection (see instructions below for changing IP address).The current list of settings is included in the file here. Note our device was used previously by another project, so while these are the current settings they may not be the default settings.Note the listing is provided here for reference only; we do not need to query or set these parameters in software.
View file | ||
---|---|---|
|
Required Telemetry
...
Parameter
...
Report Frequency
...
Purpose
...
Notes
...
Temperature of each thermal sensor
...
Once per minute
Status | ||||
---|---|---|---|---|
|
(Set by Sensor Read Frequency value)
...
...
Sensor Name Look-up Tables
Each sensor has a unique ID that is used by the LinkHub-E base. The IDs are not easily remembered so we’ll want a look-up table to tie the sensor IDs to a KPF sensor location.
...
KPF Long Name
...
KPF Short Name
...
Sensor ID
...
Notes
...
e.g. Exposure Meter Enclosure
...
e.g. 2890F1DD06000089
...
Required Alarms
...
Parameter
...
Threshold
...
Notes
...
Temperature too high
(one alarm per sensor)
...
TBC
...
Temperature too low (TBC)
(one alarm per sensor)
...
Thermal Sensor Locations (Spectrometer and Hallway) contains the list of sensor locations.
...
Relevant Datasheets & Manuals
Description | File | Source | |||||
---|---|---|---|---|---|---|---|
1 | LinkHubE User Guide |
| |||||
2 | LINK Family Manual |
| https://cdn.shopify.com/s/files/1/0164/3524/files/The_LINK_Family_Manual_1.7.pdf?7145028656254187831 | ||||
3 | Command Reference |
| |||||
4 | Sensor Datasheet Sensor was originally developed by Dallas Semiconductor but they are now owned by Maxim Integrated |
|
Relevant Software
Description
File
Source
LinkHub_E_python.py is the main program.
LinkHub_E_commands.py contains functions called by the main program.
This code finds all of the sensors connected to the LinkHub E, and then reads their values.
Note first reading might report all temperatures as ‘85’; this seems to be a consequence of the first read to find sensor IDs.
The sensor IDs and values are read into a list format.
Note this software does not differentiate between the 4 possible cables connected to the base unit; all sensors from all cables are added together into the same list.
View file | ||
---|---|---|
|
View file | ||
---|---|---|
|
Simplified by S. Gibson to remove sections not relevant to KPF.
...
Installation Instructions
Description | File | ||||
---|---|---|---|---|---|
Instructions on how to change the device’s IP address over Telnet |
|
Dispatcher Implementation
This dispatcher is part of kpfmet (currently.)
There are an arbitrary number of sensors for the unit. The names, denoted as $(NAME), are stored in the configuration file, as are the ID or address values. Readout is done in serial for the device, and done in the order of appearance in the configuration file. The “#” denotes the dispatcher number. Currently that is 4 for the kpfmet service but if dispatcher is moved or the service rearranged, this could change.
...
Keyword
...
Value
...
Type
...
$(NAME)
...
Temperature in deg C
...
Double - read only
...
$(NAME)_ID
...
ID value
...
String - read only
...
LINKSTA
...
0 - Done
1 - Reading
When Reading, the temperature values are being retrieved and the values will appear in the keywords.
Reading values is slow, so this update only reads 10 values at a time, looping through so that each value is eventually read.
...
Enumerated - read only
...
MODEL#
...
Model of the hub, value of the command ' '.
...
String - read only
...
DISP#CLK
...
Number of whole seconds dispatcher has been alive
...
Integer - read only
...
DISP#ERR
...
Error value
...
Integer - read only
...
DISP#MSG
...
Message from the dispatcher
...
String - read only
...
DISP#REQ
...
Last keyword requested to be modified, written before modify is sent.
...
String - read only
...
DISP#MEM
...
Memory used by dispatcher in kB
...
Integer - read only
...
DISP#STA
...
Status of the dispatcher
0 - Ready - working
1 - Initializing - only true during start up
2 - Shutting down - A control-C or the stop command has been issued
3 - Connecting - Attempting to connect to the device
4 - Not Connected - No connection to the device
...
Enumerated - read only
...
DISP#STOP
...
Stop command which ends the dispatcher.
0 - Continue
1 - Stop
...
Enumerated
...
DISP#CONN
...
IP address and port number separated by a colon.
...
String - read only
...
DISP#DEV
...
Device name
...
String - read only
Configuration File
The required sections are:
device which has the first four configuration keyword value pairs
dispatcher which has the dispnum value
[0], [1], [2], … [number-1] - A section for each sensor, starting from 0, and the total number must match the value of the number configuration. Extra sections are ok, but if any are missing the dispatcher will throw an error message and exit.
Configuration
Value
Explanation
ip_address
192.168.23.184
IP address of device
port
10001
Port for telnet connection to device
number
31
The number of active sensors
poll_time
20
The time between requests for temperature measurements
dispnum
4
Number of the dispatcher in the service
name
temp0
The human readable name requested for a temperature value, will set the keyword name
id
2890F1DD06000089
The ID value for the temperature measuring device on the hub. This is what will be referenced.
Note- This is the reverse of the order that the ID number is returned when querying the device. There is a swap of byte order and this is the ID that must be used for a lookup