Sub-system PDUs (needed and/or already installed)

Sub-system

Function

Physical Location

Status

Keyword Control

DEIMOS private network switch

Manage private network

K2 Computer Room. DEIMOS rack.

PDU installed

YES

DEIMOS primary host (polo)

Science and FCS CCD high-level software, ion pump dispatchers, PDU software for ion pump controllers

K2 Computer Room. DEIMOS rack.

PDU installed

YES

DEIMOS secondary host (keamano)

Motion control daemons

K2 Computer Room. DEIMOS rack.

PDU installed

YES

DEIMOS rotator control host (roto)

Rotator software

K2 Computer Room. DEIMOS rack.

PDU installed

YES

FCS CCD VME crate

FCS detector low-level software

K2 Computer Room. DEIMOS rack.

PDU installed

YES

Science CCD VME crate

Science detector low-level software

K2 Computer Room. DEIMOS rack.

PDU installed

YES

DEIMOS Virtual Machine (vm-deimos)

Autofill, FCS configuration, monitoring, sounds, and auxiliary daemons

K1 Computer Room. UNO readiness of VM rack is to be requested by Computer Support.

No PDU available

NO

Keyword history machine (moolelo)

DEIMOS keyword history dispatcher

K1 Computer Room. TCSU rack.

PDU installed

YES

Sybase server (waiaha)

DEIMOS configurable elements database

K1 Computer Room. This is a VM. UNO readiness of VM rack is to be requested by Computer Support.

No PDU available

NO

Guider host computer (waimanu)

Guider control software

K2 Computer Room. DEIMOS rack.

PDU installed

YES

Barrel Lantronix terminal server

Serial communications with ion pump controllers, slitmask barcode reader, tent mirror piezo controller, Galil 1500 controllers for optomechanical stages.

DEIMOS electronics ring Bay 3. PDU 192.168.6.40 outlet A8.

PDU installed

YES

Guider camera controller

Controller for guider camera

DEIMOS electronics ring Bay 2. Remote power control available.

No PDU needed

YES

SCSI to fiber converteer

Guider camera communications and data transfer

DEIMOS electronics ring Bay 2. Remote power control available.

No PDU needed

YES

HP 34970A data logger

Read temperature sensors located on the instrument structure

DEIMOS electronics ring Bay 2.

No PDU needed

N/A

PI P-845 piezo controller

Controller for tent mirror piezo actuator

DEIMOS electronics ring Bay 2. PDU 192.168.6.40 outlet A7.

No PDU neededinstalled

YES

Galil 1500 motion controller #1

Calibration lamps, science filter wheel, dewar translation stage, guider filter wheel, guider focus stage

DEIMOS electronics ring Bay 1. PDU 192.168.6.40 outlet A4.

No PDU neededinstalled

YES

Galil 1500 motion controller #2

Hatch, slitmask selector, slitmask arm, grating selector, grating tilts

DEIMOS electronics ring Bay 11. PDU 192.168.6.40 outlet A3.

No PDU neededinstalled

YES

LN2 can ion pump controller

Controller for LN2 canister ion pump

DEIMOS electronics ring Bay 11. PDU 192.168.6.40 outlet A1.

PDU installed

YES

Detector dewar ion pump controller

Controller for detector dewar ion pump

DEIMOS electronics ring Bay 11. PDU 192.168.6.40 outlet A2.

PDU installed

YES

D-Link DGS-105 network switch

Communications with ion pump controllers and PDU

DEIMOS electronics ring Bay 11. PDU 192.168.6.40 outlet A5.

PDU installed

YES

10Base2 to RJ45 converter

Converter to connect DEIMOS private Thinnet BNC cable with D-Link switch

DEIMOS electronics ring Bay 11. PDU 192.168.6.40 outlet A6.

PDU installed

YES

FCS CCD controller

Controller for FCS CCD

DEIMOS electronics ring Bay 10. PDU KH 192.168.6.41 outlet A3.

PDU installed

YES

Science CCD controller

Controller for Science CCD mosaic

DEIMOS electronics ring Bay 9

No PDU needed

N/A

Science CCD controller power supply

Power supply for the science CCD controller

DEIMOS electronics ring Bay 8. PDU KH 192.168.6.41 outlet A1.

PDU installed

YES

Shutter controller

Controller for detector shutter

DEIMOS electronics ring Bay 8. PDU KH 192.168.6.41 outlet A1.

PDU installed

YES

Autofill controller

DEIMOS autofill system

DEIMOS cradle Bay A. PDU KE 192.168.6.42 outlet A8.

PDU installed

YES

Galil DMC-4240 motion controller

Rotator controller

DEIMOS cradle Bay C. PDU KE 192.168.6.42 outlet A7.

PDU installed

YES

Cradle Lantronix terminal server

Serial communication with CCD controller UPS and handheld barcode reader

DEIMOS cradle Bay D. PDU KE 192.168.6.42 outlet A1.

PDU installed

YES

Netgear EN104 hub

10Base-T Ethernet hub for rotator Galil controller and barrel Lantronix terminal server

DEIMOS cradle Bay D. PDU KE 192.168.6.42 outlet A2.

PDU installed

YES

Over-temperature Cut-out AC Box

Interlock to protect instrument electronics in case of over-temperature.

DEIMOS cradle Bay A. PDU KD 192.168.6.43 outlet A3 (to be installed)

No PDU available

NO

Additional information

  • A power glitch or power cycling the DEIMOS rotator Galil controller trips the cradle interlock. The only way to recover is to physically toggle the cradle breaker in the rotator power panel next to the cradle Bay B (Over-temperature Cut-out AC Box). This behavior needs to be addressed to make DEIMOS UNO ready.

  • Facility power glitches can trip the DEIMOS rotator E-Stop which cuts power to the rotator motor. The only way to recover from the E-Stop is to have a person physically press the green reset button located in the DEIMOS cradle Bay C per DEIMOS rotator controller E-stop recovery procedure. Arguably, a person physically next to DEIMOS to recover from an E-stop is desirable for safety reasons, but we should be aware that a facility power glitch on a DEIMOS observing night without personnel on the summit will require sending someone to the summit to press the DEIMOS E-stop reset button.

  • All four components in the DEIMOS cradle can be connected to an 8-port PDU to be installed in Bay D. A power cable for the autofill controller would need to be routed from Bay A to be D. There is already a power cable from the rotator controller in Bay C to Bay D.

  • Theres is already an 8-port PDU installed in the DEIMOS electronics ring Bay 11. This PDU is in the DEIMOS private network controller via the deipower keyword service. Four of the ports are currently used for the two ion pump controllers, D-Link network switch, and 10base2 to RJ45 converter. The remaining PDU ports can potentially be used to plug in the two Galil 1500 motion controllers in Bays 1 and 11 respectively, the PI piezo controller in Bay 2, and the barrel Lantronix terminal server in Bay 3.

  • It is not clear if keeping the current ThinNet private network is the best way forward for UNO and the upcoming DEIMOS detector upgrade. We may need to submit a Continuous Improvement project to replace the current ThinNet infrastructure with either fiber or copper Ethernet.

  • If we do not add a second PDU to the DEIMOS electronics ring, there will be 3 devices left without PDU power control: science CCD controller power supply and shutter controller in Bay 8, and FCS CCD controller in Bay 10.

...