Here is a list of the actions that make up the MOSFIRE testAll
Ping various computer/network hardware to confirm they are aliveStatus colour Red title NOT a KEYWORD kaimama
control1
eds1
mpulizzi1
mpulizzi2
iolan1, control1, eds1, mpulizzi1, mpulizzi2, iolan1
Check lastalive keyword on software (Servers)Status colour Green title IS A KEYWORD mosfire, mcsus, mdhs, mds, mfcs, mmdcs, mmf1s, mmf2s, mmgss, mmgts
mmprs
mp1s
mp2s
mpas
mscs
mtcs, mmprs, mp1s, mp2s, mpas, mscs, mtcs
Verify PIDs exist for softwareStatus colour Red title NOT A KEYWORD write_image
fcstrack
ds9relay
lickserv, fcstrack, ds9relay, lickserv
Check daemons (only if observing)Status colour Green title IS A KEYWORD watchrot
watchslew
watchfcs
autodisplay, watchslew, watchfcs, autodisplay
Verify power statusStatus colour Green title IS A KEYWORD glycol_power = on, CSU_controller_power = on, CSU_drives_power = on, Jade2_power = on, computer_power = on, Lantronix_power = on, guider_focus_power = on, ion_pump_power = on, MAGIQ_guider_power = on, temp_control_power = on, motor_box_power = on, power_supply_power = on, FCS_controller_power = on, dewar_heater_power = on, CCR_1_power = on, CCR_2_power = on
Verify stagesStatus colour Green title IS A KEYWORD dust cover, : mmdcs status is OK, filter wheel 1, : mmf1s status is OK, filter wheel 2, : mmf2s status is OK, grating turret, : mmgts status is OK, grating shim, : mmgss status is OK, pupil rotator, : mmprs status is OK or TRACKING, CSU, : mcsus status is OK
Check SettingsStatus colour Green title IS a KEYWORD glycol flow (mdhs glysup = Flow)
detector temp (mtcs curtmp1 = 77 +/- 0.1)
bulkhead temp (mtcs curtmp2 = 120 +/- 1)
CCR remote control (mscs chremote = 1)
CCR 1 Speed (mscs dacout1r = 45 +/- 1)
CCR 2 Speed (mscs dacout2r = 45 +/- 1)
window heater voltage (mdhs tmp5 = 17.5 +/- 1.5)
CSU electronics temp (mdhs tmp2 = 0-30)
cabinet temp (mdhs tmp3 = 0-30)
thermocouple pressure (mpas g1str = 0-1e-4)
ion pump 1 pressure (mpas g3str = 0 - 1e-7)
ion pump 2 pressure (mpas g4str = 0 - 1e-7)
cabinet door status (mdhs ebaydoor = Closed)
FCS correcting (mfcs active = 1)
datataking system (mds ready = 1)
current instrument (dcs currinst = mosfire)
...