Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Instrument

Current alarm implementation and where they run

Who are alerts sent to?

Alert Method (ie email?)

How much advance warning time provided before warm up?

Other Comments

Hires

KPF

LRIS blue

LRIS red

Mosfire

Osiris

ESI

Nirspec

Nirc2

Deimos

KCWI blue

Blue lakeshore measures and controls blue detector temperature via kt1s TMP1, monitored by kcwimon TEMPBLUEDET

kcwi_info@keck.hawaii.edu

email

Alarm if:

  • below -158.1 deg C for >1min

  • above -108.1 deg C for >1min

  • not broadcasting temps for >10min

blue detector target temp is -110.1 deg C

KCWI red

Red detector controller measures and controls red detector temperature via krds TEMPDET, monitored by kcwimon TEMPREDDET

kcwi_info@keck.hawaii.edu

email

Alarm if:

  • below -130 deg C for >1min

  • above -126 deg C for >1min

  • not broadcasting temps for >10min

red detector target temp is -125.0 deg C

Nires

AO ?