Table of Contents:
Introduction
Relevant Devices
Description | Qty | Source | Part Number |
---|---|---|---|
VED24 Shutter Controller | |||
DSS25B Shutter | |||
larger shutter | |||
Relevant Functional Block Diagram
Installation Instructions
The shutter controller has a set of DIN “Function Switches” (second from right in image below) and an Octal switch for “Pulse Duration” (far right in image below) that need to be configured for the particular shutter being used:
For the DSS25B shutter which is used with the CaHK system, the settings are:
The setting for Switch 1 does not depend on the shutter type, but should be set to ‘UP’ for ‘LOCAL’ (this disables the USB port and enables the BNC Pulse Input):
Note that there is also a toggle switch on the front that sets the ‘Normally Open’ or ‘Normally Closed’ polarity of the switch (second from left in image above). The manual is not clear on how this affects a bi-stable shutter. For consistency within KPF, all shutter controllers should be set to ‘N.O.’.
To manually operate a shutter, click this switch back and forth. Be sure to leave it at ‘N.O.’ when done.
cables in PN and diagram (same with Galil Enclosure)
For the cable between the VED24 and the DSS25B shutter, it is a Uniblitz SM203D, which ships with the VED24.
picture of NO sticker
Relevant Datasheets & Manuals
Description | File | Source | |
---|---|---|---|
1 | Shutter Controller Manual | ||
2 |
Relevant Software
Description | File | Source | |
---|---|---|---|
1 | |||
2 |
0 Comments